How to solve the problem of zero or low calorific value of electric heat tracing system

发布时间:

  • File size: 13.0KB

►  Reason (1)

The power supply tends to zero or is low;

►  Corrective Methods

overhaul of the power supply system;

 

►  Reason (2)

Some of the fittings are not connected or the electric heat trace is cut off;

►  Corrective Methods

Overhaul the accessories and electric heat tracing, recalculate the should calorific value (PA) of the circuit, and compare it with the design power (PI);

 

►  Reason (3)

There are improper connections in some accessories;

►  Corrective Methods

Tighten the accessories and electric heat tracing, and tighten the screws at each connection point;

 

►  Reason (4)

The thermostat is incorrectly adjusted to the state of being turned off;

►  Corrective Methods

readjust the thermostat;

 

►  Reason (5)

1. The pipeline is in a high temperature state, and the electric heat trace has been damaged;

2. The electric heat trace has been damaged by exposure to excessive ambient temperature;

3. The electric heat trace has been damaged by exposure to moisture;

►  Corrective Methods

Measure the temperature of the pipeline and recalculate the heat generation (PA), if the design power (PI)/heat generation (PA) is less than 0.75, replace or supplement the electric heat tracing;